Company InfoContact UsPoliciesDistributors
Hello, Guest Call Toll FREE 800-697-8665
Shopping Cart: 0 item(s) / Total: $0 log out
Untitled Document
Home > New Products
CA10-AC Circuit Analyzer
CA10-AC Circuit Analyzer
Item Id: CA10
Product Description
Ideal for identifying 110/220V AC power circuit and wiring problems that can cause shocks, sparks, fires, equipment failures and poor equipment performance

MSRP: Visit a certified dealer to purchase this product.
Availability:
Purchase through our Certified Internet Retailers
Email a friend
Share |
Ideal for identifying 110/220V AC power circuit and wiring problems that can cause shocks, sparks, fires, equipment failures and poor equipment performance.
Related Products
CBL20 - CBL20- Ac Circuit Analyzer
Cbl20
MSRP: Visit a certified dealer to purchase this product.
    

Features:

  • Measures a branch circuit’s line voltage, peak voltage and neutral-to-ground voltage
  • Calculates a circuit’s voltage drop in response to 12A,
    15A and 20A loads
  • Measures the impedance of hot, neutral and ground
    conductors as well as available short-circuit current
    (ASCC)
  • Identifies wiring configurations and detects wiring faults
    and missing ground wires
  • Tests the reliability and response time of GFCIs (ground
    fault circuit interrupters) and RCDs (residual current
    devices)
  • Displays True RMS readings of all voltages except peak
    voltages
  • Works with 2- and 3-phase circuits
  • Jumbo LCD with 30-second backlight
  • Familiar menu/sub-menu operation
  • Data HOLD button and 30-minute auto power off
  • Powered by six “AAA” batteries (included)
  • 1 year limited warranty
 


    

Specifications:

Parameter


Measurement Range Measurement AccuracyDisplay Resolution
Line Voltage85 to 265VAC±1.0% ± 0.2V0.1V
Peak Voltage121 to 374VAC ± 1.0% ± 0.2V 0.1V
Line Frequency45 to 65 Hz± 1.0% ± 0.2Hz0.1Hz
Voltage Drop0.1 to 99.9%± 2.5% ± 0.2%0.1%
Load Voltage10 to 265V± 2.5% ± 0.2V0.1V
Neutral-to-Earth Voltage0 to 10VAC± 2.5% ± 0.2V0.1V
Hot, Neutral and Ground Line Impedance0 to 3Ω>3Ω ± 2.5% ± 0.02Ω0.01Ω
GFCI Triggering Time1ms to 6.5 sec.± 1.0% ± 2ms 1ms
RCD Triggering Time1ms to 6.5 sec.± 1.0% ± 2ms1ms
RCD Triggering Current30 to 37mA± 1.0% ± 0.2mA0.1mA
Operating/Storage Temperature32° to 122°F (0° to 50°C) @ <80% RH  
Dimensions7.6 x 3.1 x 1.5 in. (193 x 78 x 39mm)  
Weight (without Batteries)10.4 oz. (295g)  

Includes:      

  • 12 AWG
  • 20 in. (0.5m) Long Test Cable
  • Six “AAA” Batteries
  • Soft Carrying Case
  • User’s Manual
  • 1 Year Limited Warranty